Perkins Diesel Engine Specifications


Perkins Diesel Generators
MODEL
60 HZ. 
50 HZ.  
Dimensions
WEIGHT
IN
1800 RPM
1500 RPM
UNIT
ENGINE
EMERG.
PRIME
EMERG.
PRIME
L" x W" x H"
LBS.
P-23
3.152.4
23
21
18
16
60" x 38" x 50"
1,057
P-28
3.152.4
28.5
26
24
22
60" x 38" x 50"
1,057
P-30
4.236
30
27.5
26
25
60" x 34" x 50"
1,531
P-40
4.236
40
36
33
29
72" x34" x 51"
1,695
P-60
T4.236
60
54
50
40
72" x34" x 51"
1,713
P-75
1004-TG
75
67
57
52
72" x 34" x 52"
1,872
P-96
1006-TG1A
96
87
83
75
91" x 38" x 57"
2,310
P110
1006-TG2A
107
97
91
83
91" x 38" x 60'
2,403
P130
1006-TAG
132
121
120
109
91" x 38" x 60'
2,403
P-150
1306-9TG1
153
139
133
121
110" x 48" x78"
4,147
P-175
1306-8TAG1
175
170
145
140
110" x 48" x78"
4,147
P-200
1306-9TAG
203
185
183
166
110" x 48" x78"
4,147
               

  • STANDARD EQUIPMENT: The engine and the generator are mounted on a steel base on vibration isolators, There is a fuel tank integrated, radiator for tropical conditions, industrial silencer with rain cap. The complete unit is tested to full load plus 10% in a load bank
  • PERKINS ENGINE :
    Diesel, water radiator cooled, mechanical governor, industrial air filter, 12 Vcd motor Start and battery charging alternator, Automatic stop protection for failures of high water temperature and low lubricating oil pressure.
  • ALTERNATOR:
    Brushless with one bearing directly coupled to the engine. With automatic voltage regulator.
  • AUTOMATIC STOP PROTECTION:
    For failures of high water temperature and low lubricating oil pressure.
  • INSTRUMENT PANEL: Mounted on the unit on vibration isolators model M6 with voltmeter, ammeter, with A/V selector switch, hour counter, frequency and RPM meter, main key start switch.
  • OPTIONS: These units are assembled according to the customer’s requirements and therefore they can have all the options required by the customer like: weather or sound attenuation enclosures, automatic transfer switches, or any other type of electrical controls, even computerized.